Research (November 2026, Applied Thermal Engineering, Volume 308) showed that combining superhydrophobic copper properties with millimeter-scale geometric protrusions can passively slow icing on surfaces in cooling systems and heat pumps.
👩🔬 Scientists Xiaohang Zhu, Shuai Chen, Yunhao Ma, Yanwei Hu, and Yurong He found that:
- the onset of freezing on such surfaces is delayed by 1.9 times compared with conventional copper;
- the average width of ice-free zones increases by 34%;
- with optimization of the height, pitch, and width of several protrusions, the share of areas protected from icing reached 93.98%.
The problem of frost formation on cold heat exchanger surfaces remains one of the key causes of:
- reduced heat transfer efficiency;
- increased energy consumption
in refrigeration equipment and heat pumps, especially under humid conditions.
The researchers used experimental methods and water vapor diffusion modeling to assess the combined impact of:
- the surface’s water-repellent properties;
- its geometry
on the icing process, avoiding active defrost methods.
The mechanism of action is that millimeter-scale protrusions change the distribution of water vapor:
- at the tops of the protrusions, vapor condenses more intensely;
- in the gaps between them, vapor transport is limited.
The superhydrophobic coating reduces the droplet contact area and makes it harder for ice bridges to form between droplets, causing icing to spread more slowly.
The authors also measured:
- frost thickness;
- frost mass;
- apparent frost density,
confirming that surface geometry affects not only the time to freezing onset but also the pattern of frost accumulation.
The results indicate the promise of a passive approach to icing management when designing heat pump evaporators and heat exchangers for refrigeration equipment.
⚠️ However, the authors emphasize that the data relate to controlled laboratory conditions and do not allow a direct assessment of energy-use reduction in real systems; implementation requires additional tests for:
- coating durability;
- heat transfer;
- defrost energy consumption.